| S.I. | S.I. R | U.S. | U.S. R | U.S. Customary Units are approximate |
|---|---|---|---|---|
| mm | K·m²/W | in | °F·ft²·h/Btu | Also non-SI 1 m²·K/W or 1 °C·m²/W = SI 1 K·m²/W |
| 60 | 1.6 | 2.4 | 9.2 | Joists are left exposed1,3 |
| 80 | 2.2 | 3.1 | 12.3 | Will have significant thermal bridging1,3 |
| 100 | 2.7 | 3.9 | 15.3 | Covers joists2,3 |
| 110 | 3.0 | 4.3 | 16.9 | Design limit of AS 3000 partially surrounded wiring2,3,4 |
| 120 | 3.2 | 4.7 | 18.4 | |
| 130 | 3.5 | 5.1 | 20.0 | |
| 140 | 3.8 | 5.5 | 21.5 | |
| 150 | 4.1 | 5.9 | 23.0 | AS 3000 allows for 150 mm of lower performance insulation |
| 160 | 4.3 | 6.3 | 24.6 | Values used in cold climates where heating is usual |
| 180 | 4.9 | 7.1 | 27.6 | |
| 200 | 5.4 | 7.9 | 30.7 |
Notes: -
Higher values can be supplied, however we recommend that you seek advice from an engineer, electrical contractor or the supply authority before you specify values higher than R 3.0. For new buildings you can arrange to have wiring that is not surrounded by placing the wiring 200 mm or more above the ceiling.
An economical R value can be calculated using a basic return on investment model, however the improvement is reduced [1] as more insulation is used. There are also practical considerations including the actual performance [2][3] of various products.
Note that the R value of insulation is not simply added to the existing R value of your building [2][3] and that the achieved system R value must work with the air sealed within the building [4][5] to regulate temperature.
R-for-R all insulation is NOT created equal! [CIMA]
Cellulose - Naturally Better Insulation

Email