AS/NZS 3000:2007
AS/NZS 3000:2007 4.5.2.3 "Recessed luminaires" has a number
clauses.
- 4.5.2.3.a.i does not conform to AS/NZS 60598.
- 4.5.2.3.a.ii matches AS/NZS 60598 requirements for insulating
ceilings.
- 4.5.2.3.b says fire-resistant, but AS/NZS 60598 limits surface
temperature.
- 4.5.2.3.c even with a small gap this will defeat thermal insulation.
- 4.5.2.3.d has been shown to
defeat thermal insulation.
AS/NZS 3000:2007 4.5.2.3 "Recessed luminaires" also has a number
of notes which according to the SA technical regulator are
mandatory.
- National Building Codes require the installation of
thermal insulation in many situations.
- AS/NZS 60598.1 and AS/NZS 60598.2.2 detail the test
method and the maximum surface temperatures permitted for recessed
luminaires.
NOTE 1 is a requirement of the BCA. Meeting this requirement is
not possible with 4.5.2.3.d and also may not be possible with
4.5.2.3.c. See my calculations.
This means clearances must be
significantly reduced so that NOTE 2 also applies. This just leaves
4.5.2.3.a.ii as the only valid option.
Deleting clause 4.5.2.3.a.i, 4.5.2.3.c and 4.5.2.3.d and default
clearances from AS/NZS 3000:2007 and aligning clause 4.5.2.3.b
with AS/NZS 60598.1 and AS/NZS 60598.2.2 would clarify
this situation. I have therefore struck out 4.5.2.3.a.i, 4.5.2.3.c
and 4.5.2.3.d and the text and figure that it relates to. I have
also changed clause 4.5.2.3.b.
With all these deletions it may now be limiting. The Recessed
luminaires section could be split to cover cases where:
- insulation is installed, is to be installed later or may be
installed later; and
- insulation can never be installed.
Andrew Buckeridge ACIMA
The original AS/NZS 3000:2007 text with my
(comments), deletions and
changes.
4.5.2.3 Recessed luminaires
Recessed luminaires and their auxiliary equipment shall be
installed in a manner designed to minimize temperature rise and
prevent the risk of fire.
The temperature rise at the rear of a recessed luminaire shall
be limited to prevent damage to adjacent materials.
This requirement shall be satisfied by one of the following
methods:
- The use of a luminaire specifically designed and
certified by the manufacturer to permit-
contact with combustible materials;
or
(The
mark is not appropriate for
insulating ceilings.
The scope of this clause is Recessed luminaires for which AS/NZS
60598 requires insulation cover as below.)
- enclosure or covering by thermal insulation material
,
as appropriate to the location of the luminaire.
(Only the
mark is appropriate for insulating
ceilings.
The scope of this clause is Recessed luminaires so location here is
meaningless.)
Installation of the luminaire within a suitable
fire-resistant enclosure.
Installation of the luminaire within an enclosure specifically
designed and certified by the manufacturer to permit enclosure or
covering by thermal insulation material.
Provision of required clearances from combustible and
thermal insulating material as specified by the manufacturer of the
luminaire.
Provision of the default clearances from combustible
and thermal insulating material as specified in Figure
4.7.
Where manufacturer's installation instructions that
specify required clearances are not available, the luminaire shall
be installed in accordance with (b) or (d).
NOTE:
In the case of a suitably designed luminaire, the
installation instructions may specify that no clearance is
required.
Recessed luminaires and their auxiliary equipment shall
be installed in such a manner that necessary cooling air movement
through or around the luminaire is not impaired by thermal
insulation or other material.
Where thermal insulation is of a type that is not fixed
in position, e.g. loose fill, a barrier or guard constructed of
fire-resistant material shall be provided and secured in position
to maintain the necessary clearance (see Figure 4.7).
Where thermal insulation may reasonably be expected to be
installed in the space containing a recessed luminaire, the
luminaire shall be installed in such a manner as to provide for the
subsequent installation of thermal insulation. (This puts
requirement clearly.)
Recessed luminaires shall be installed in accordance with (a) or
(b), or provided with equivalent protective measures, where there
is a likelihood of extraneous combustible material, e.g. leaves or
vermin debris, etc., collecting on or around the luminaire.
NOTES:
- National Building Codes require the installation of
thermal insulation in many situations.
- AS/NZS 60598.1 and AS/NZS 60598.2.2 detail the test
method and the maximum surface temperatures permitted for recessed
luminaires.
These maximum temperature limits must be
satisfied to permit any reduction in the default values of Figure
4.7.
Building element above fitting
Barrier required for |
loose fill insulation _Transformer | Building
or loose combustible / 50 mm A structural
materials / |-----| | B member
\ (()) | __|__ |-----------|
~~~~~~~~~~~~~~~~~~~| | | | | |_______
| | / \ | | \ / |
Thermal insulation | C | / \ | | |
|-----------|/ ( X ) \| | / \ |
_______________________________| |____________________
=================
Recessed luminaire
|
Dimension |
Incandescent lamp |
Halogen lamp |
A - Clearance above luminaire |
50 mm |
200 mm |
B - Side clearance to structural member |
100 mm |
200 mm |
C - Clearance to thermal insulation |
50 mm |
200 mm |
D - Clearance to supply transformer |
50 mm |
FIGURE 4.7 DEFAULT MINIMUM CLEARANCES FOR
RECESSED LUMINAIRES |
COPYRIGHT